12 17.5 24kV Ime ụlọ Vacuum circuit Breakers, GPVN-E Series
Ọnọdụ gburugburu
Ọnọdụ okpomọkụ: -25℃~+45℃, nkezi kwa ụbọchị: ≤35℃
Elu: 1000m (Standard);nwere ike ruo 4500m maka ịtụ pụrụ iche;
Iru mmiri dị ala: nkezi kwa ụbọchị ≤95%, nkezi kwa ọnwa ≤90%;
Ike ala ọma jijiji ≤8 ogo;
Oge ọdabara kwesịrị ịbụ nke enweghị ọkụ, ihe mgbawa, ihe corrosives na ịma jijiji siri ike.
Nlereanya
GPVN -12Kv/17.5kV Ime ụlọ AC High Voltage Vacuum circuit Breaker
Nkọwa nka nka
Mba. | Ihe | Nkeji | Data | ||||||
1 | Egosiri voltaji | kV | 7.2-12 (15/17.5) | ||||||
2 | Ugboro ugboro | Hz | 50/60 | ||||||
3 | Enyere ugbu a | A | 630,1000,1250 | 1600 | 2000,2500,3150 | 4000 | |||
4 | Enyere ogo mgbawa nke mkpirisi okirikiri | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
5 | Enyere mkpirisi okirikiri ime ugbu a | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
6 | Obere oge na-anagide ugbu a | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Ogo kacha elu na-anagide ugbu a | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Enyere ọkwa ndọpụ na-agbaji ugbu a | kA | 12.6 | 12.6 | 16 | 16 | 20 | ||
9 | Egopụtara mmejọ nke na-agbaji ugbu a na-apụ apụ | kA | 17.4 | 21.7 | 27.4 | 27.4 | 34.7 | 34.7 | 43.5 |
10 | Enyere ọkwa mkpirisi okirikiri na-agbaji oge nbibi ugbu a | Oge | 50 | 30 | 30 | 12 | |||
11 | Enyere usoro ọrụ | O-0.3s-CO-180s-CO | O-180s-CO-180s-CO | ||||||
12 | Egotara nbibi ugbu a nke otu ụlọ akụ capacitor | A | 630 | ||||||
13 | Egotara nbibi nke ugbu a nke ụlọ akụ capacitor azụ na azụ | A | 400 | ||||||
14 | 1 min.Ugboro ike na-eguzogide voltaji | kV | Usoro nke usoro/ ruo n'ụwa: 42, gafee kọntaktị mepere emepe:48 | ||||||
15 | Ọkụ ọkụ na-eguzogide voltaji | kV | Usoro na-aga n'ihu/ ruo n'ụwa: 75, gafee kọntaktị mepere emepe:85 | ||||||
16 | Ndụ mechanical | Oge | 20000 | ||||||
17 | Oge mmechi | ms | ≤75 | ||||||
18 | Oge mmeghe | ms | ≤60 | ||||||
19 | Oge nchekwa ike n'okpuru voltaji agbagoro | s | ≤10 |
Nkọwapụta akụkụ nke GPVN-12E
GPVN-24□ Ime ụlọ AC High Voltage Vacuum circuit Breaker
Nkọwa nka nka
Mba. | Ihe | Nkeji | Data | |||
1 | Egosiri voltaji | kV | 24 | |||
2 | Ugboro ugboro | Hz | 50/60 | |||
3 | Enyere ugbu a | A | 630 1250 1600 2000 2500 3150 4000 | |||
4 | Enyere ogo mgbawa nke mkpirisi okirikiri | kA | 20 | 25 | 31.5 | 31.5 |
5 | Enyere mkpirisi okirikiri ime ugbu a | kA | 50 | 63 | 80 | 80 |
6 | Enyere akara okirikiri mkpirisi na-eguzogide ugbu a(4s) | kA | 20 | 25 | 31.5 | 31.5 |
7 | Ogo kacha elu na-anagide ugbu a | kA | 50 | 63 | 80 | 80 |
8 | Egopụtara mgbaji ọkụ na-enweghị nzọụkwụ | kA |
|
| 12.6 | 12.6 |
9 | Enyere nbibi ugbu a nke mmejọ ụwa na-apụ apụ | kA | 17.4 | 21.7 | 27.4 | 27.4 |
10 | Enyere oge nbibi nke mkpirisi mkpirisi mgbaji dị ugbu a | Oge | 50 | |||
11 | Enyere usoro arụ ọrụ |
| O-0.3s-CO-180s-CO | |||
12 | Egotara nbibi ugbu a nke otu ụlọ akụ capacitor | A | 630 | |||
13 | Egotara nbibi ugbu a nke ụlọ akụ capacitor azụ na azụ | A | 400 | |||
14 | 1 min.Ugboro ike na-eguzogide voltaji | kV | 50 | |||
15 | Ọkụ ọkụ na-eguzogide voltaji | kV | 125 | |||
16 | Ndụ mechanical | Oge | 20000 | |||
17 | Oge mmechi | ms | 75 | |||
18 | Oge mmeghe | ms | 60 | |||
19 | Oge nchekwa n'okpuru voltaji agbagoro | s | 10 |