Ngwa ejikọtara ngwa nbinye ọkụ ọkụ ọkụ
Nlereanya na Pụtara
Ọnọdụ gburugburu
Okpomọkụ gburugburu: Max.temp.+ 40 ℃;Min.temp.-15 ℃
Iru mmiri gburugburu: iru mmiri dị ala kwa ụbọchị ≤ 95%;Iru mmiri dị ala kwa ọnwa ≤ 90
Elu saịtị ebe ọrụ Switch dị nwere ike iru 1000m
Maka ọnọdụ ọrụ pụrụ iche, biko kpọtụrụ onye nrụpụta
Ụkpụrụ ntụaka
GB3804-2004 High-Voltage ọzọ-ugbu a switches maka gosiri voltaji n'elu 3.6kV na ruo na gụnyere 40.5kV.
GB16926-2009 Ngwakọta mgba ọkụ dị ugbu a-Voltaji dị elu
GB/T11022-1999 nkọwa ndị a na-ahụkarị maka mgba ọkụ voltaji dị elu na ụkpụrụ njikwa.
Isi nka nka nke mgba ọkụ
Aha | Nkeji | Gbanwee GPL-24/T630-20 | Nchikota ngbanwe-fuse GPLR-24/T125-40 | |
Egosiri voltaji | kV | 24 | 24 | |
Ugboro ugboro | Hz | 50 | 50 | |
Enyere ugbu a | A | 630 | 125 (dị ka fuse) | |
Enyere aha Mkpuchi ọkwa | 1min ugboro ike na-eguzogide voltaji | kV | Njikọ ọnụ na ndị na-agbaji meghere 65; Usoro na-aga n'ihu, nkeji ruo n'ụwa 65 | |
Mkpali ọkụ na-eguzogide voltaji | kV | Usoro nke oge, nkeji ruo n'ụwa 125; Kọntaktị ọnụ nwere ndị kewapụrụ emeghe 125 | ||
Enyere oke mgbawa sekit dị mkpụmkpụ | kA | - | 40 | |
Ibu na-agbaji ugbu a | A | 630 | - | |
Enyere akara akaghị mmechi na-agbaji ugbu a | A | 630 | - | |
Ibu na-arụ ọrụ obere nkwụsịtụ ugbu a | A | 31.5 | - | |
Enyere ogo ọcha na-agbaji ugbu a | A | 16 | 16 | |
Obere sekit dị mkpụmkpụ na-eme ugbu a (elu) | kA | 50 | 100 | |
Enyere obere oge na-eguzogide ugbu a | kA | 20 | - | |
Obere oge kwadoro ogologo oge dị ugbu a | S | 4 | - | |
Ogo kacha elu na-anagide ugbu a | kA | 50 | - | |
Enyere ọkwa iweghara ugbu a | A | - | 3150 | |
Nguzogide sekit | μΩ | ≤150 | ≤250+ Fuse | |
Ike moto | W | 90 | ||
Ịkwaga na ofu kọntaktị nwere ike ekwe omume mkpokọ mkpokọta ọkpụrụkpụ | mm | 3 | ||
Mwepu n'etiti kọntaktị mepere emepe | mm | 12±1 | ||
Oge mmechi mmechi kọntaktị | ms | ≤2 | ||
3-phase asynchronous | ms | ≤2 | ||
Nkezi ọsọ mmechi | m/s | 0.8± 0.2 | ||
Nkezi ọsọ mmeghe | m/s | 1.3 ± 0.2 | ||
Mechanical ntachi obi | Oge | 10000 |
Isi nka nka nke moto
Aha | Nkeji | Oke |
Egosiri voltaji arụ ọrụ | V | AC/DC 110/220 |
Ntinye ike nwere ogo | W | 80 |
Oke voltaji nkịtị nke moto chaja |
| 85% ~ 110% gosiri voltaji arụ ọrụ |
Oge nchaji | s | ≤15 |
Isi nka na ụzụ nke eriri igwe
Aha | Nkeji | Oke | |
Egosiri voltaji arụ ọrụ | V | AC, DC110 | AC, DC220 |
Arụ ọrụ ugbu a | A | ≤3 | ≤2 |
Oke voltaji dị nso nke eriri igwe |
| 85% ~ 110% gosiri voltaji arụ ọrụ | |
Oke voltaji nkịtị nke eriri igwe njem |
| 65% ~ 120% gosiri voltaji arụ ọrụ |
Ọdịdị na Ọrụ
Ụdị mgba ọkụ GPL (R) nwere usoro arụ ọrụ na ụlọ arc-emenyụ na nhazi azụ, isi sekit na-eduzi ya bụ usoro ihe nlereanya nke ala.A na-edozi oghere arc-emenyụ ụlọ ahụ na kọlụm vetikal mkpuchi mkpuchi nke ejiri epoxy resin site na teknụzụ APG, yabụ na-eji ezigbo mgbochi creepage dị otú ahụ imewe nke ọma nke na-ebelata mkpokọta uzuzu n'elu nke oghere arc-emenyụ ụlọ, ọ bụghị nanị na ọ nwere ike igbochi oghere imenyụ ụlọ si n'èzí mmetụta, ma nwekwara ike hụ na-eweta elu-eguzogide ọnọdụ megide voltaji mmetụta ọbụna na-ekpo ọkụ-u mmiri ihu igwe ma ọ bụ arọ mmetọ gburugburu ebe obibi.
Enwere ike ịgba ụgwọ usoro mmiri na-arụ ọrụ mmiri nke edoziri na mkpofu ụgbọ elu site na akwụkwọ ntuziaka ma ọ bụ moto, usoro arụ ọrụ dị na igbe ígwè edozi n'ihu ụlọ arc-enyụ.A na-ekewa igbe ahụ n'ime oghere mgbakọ ise site na mkpịsị aka anọ, n'ime oghere a, enwere akụkụ chaja, akụkụ mmiri mmiri, ngalaba ntọhapụ na nchekwa nke usoro iche iche.Ọdịdị nke GPL (R) ụdị mgba ọkụ nke usoro ọrụ na arc-emenyụ ụlọ na-ahaziri n'ime ihe mwekota n'ihu-azụ okirikiri nhọrọ ukwuu nwere ike dakọtara nke ọma arụmọrụ nke usoro ọrụ na arụmọrụ dị mkpa maka imebi na ime nke arc-emenyụ ụlọ.Ọzọkwa, nwere ike ibelata okwu etiti etiti na-enweghị isi ma belata mkpọtụ na ike a na-eri iji mee ka arụmọrụ GPL (R) rụọ ọrụ nke ọma.