GPN1-12kV mgbanaka mgbanaka nke igwe nwere ike mbughari AC
Ọnọdụ gburugburu
Ọnọdụ okpomọkụ: -25℃~+45℃, nkezi kwa ụbọchị: ≤35℃
Elu: 1000m (Ọkọlọtọ);nwere ike ruo 4500m maka ịtụ pụrụ iche;
Iru mmiri dị ala: nkezi kwa ụbọchị ≤95%, nkezi kwa ọnwa ≤90%;
Ike ala ọma jijiji ≤8 ogo;
Oge ọdabara kwesịrị ịbụ nke enweghị ọkụ, ihe mgbawa, ihe corrosives na ịma jijiji siri ike.
Nlereanya
Njirimara ngwaahịa
1) Ngwaahịa a na-adabara maka GPVN-12kV / 17Kv / 24kV nke agbakwunyere ma ọ bụ mkpuchi mkpuchi mkpuchi oghere ma ọ bụ ABB's VD4 vacuum circuit breaker.
2) Anyị mmepụta nhazi GPVC agụụ contactor - fuse Nchikota ma ọ bụ ABB ụlọ ọrụ VC agụụ contactors, nke nwere ike mejupụtara FC akaghị cubicle, izute ọkụ eletrik usoro nke ike osisi na ina nke ọzọ ulo oru na Ngwuputa ulo oru.
3) Iji ọmarịcha aluminum-zinc clad steel plate site na nkenke CNC machining akụrụngwa gbakọtara n'ime kabinet, na iji usoro ịgbado okpukpu abụọ, na-eme ka ike nke kabinet dịkwuo mma.
4) Ọnụ ụzọ elu site epoxy resin electrostatic powder spray process, iguzogide corrosion, oxidation, mmetụta na ike adhesion.
5) Cabinet n'ụzọ zuru ezu gbochiri Ọdịdị na-ghọtara n'ụzọ zuru ezu armored, na-arụ ọrụ nkeji na-kpamkpam iche iche.Mgbe ọnụ ụzọ na-emechi, ọ nwere ike nweta ọrụ nke sekit emebi na earthing mgba ọkụ.
6) Usoro nkenke ịghasa mbanye, hụ na trolley nwere ezigbo mgbanwe.
7) Atụmatụ izizi zuru oke iji gboo mkpa dị iche iche nke ndị ọrụ, ma na-enyere atụmatụ trolley abụọ aka.
8) Ngwa ngwa ịgbanye ala maka ala na obere sekit, yana iji nweta ọrụ eletriki (Motorized).
9) Usoro mkpọchi nke "Ise Safety" dị mfe ma dị irè nwere ike igbochi ojiji nke ọma ma hụ na nchekwa onye ọrụ.
10) Switchgear bụ nke ụdị Arc-proof, n'elu ụlọ ụgbọ ala, Vacuum circuit breaker compartment, na ọdụ ọdụ USB nwere ngwaọrụ enyemaka nrụgide.
11) Ngalaba USB nwere ohere zuru oke, enwere ike ijikọ ya ngwa ngwa na ọtụtụ eriri, ma hụ na nrụnye dị elu nke nkwụnye eriri.
12) Ogo nchebe siri ike (IP4X), iji gbochie ihe mba ọzọ ma ọ bụ mbuso agha nke ọma.
13) Usoro nke abụọ nke nhọrọ na-esote ngwaọrụ nlekota nchekwa nwere ọrụ nyocha onwe ya na nkwurịta okwu data, kọmpụta nwere ọgụgụ isi, iji nweta njikwa anya, telemetry nke dịpụrụ adịpụ, nlele anya, ngbanwe dịpụrụ adịpụ.
14) Zute GB3906, GB/T11022, DL404 na IEC60298, IEC62271-1 ụkpụrụ, na site a keukwu ule ụdị ule na plateau ule (3000 m).
15) Gafere ule ndakọrịta elektrọnik n'ụlọ nyocha nyocha akụrụngwa dị elu.
Nkọwapụta A.Technical Maka 12Kv switchgear
Ihe | Nkeji | Data | |
Egosiri voltaji | kV | 6-12 | |
Ugboro ugboro | Hz | 50/60 | |
Enyere ugbu a | A | 630-4000 | |
Enyere ọkwa mkpuchi mkpuchi | 1min ugboro ike (Oge ruo ụwa / gafee kọntaktị mepere emepe) | kV | 42/48 |
Ọkụ ọkụ na-eguzogide voltaji (Fase to earth/ofe kọntaktị mepere emepe) | kV | 75/85 | |
Nnukwu bọs ụgbọ ala gosiri ugbu a | A | 1250,1600,2000,2500,4000 | |
Sub-busbar gosiri ugbu a | A | 630,1250,1600,2000,2500,3150 | |
Egotara obere oge nagide ugbu a(4s) | kA | 16,20,25,31.5,40,50 | |
Ogo kacha elu na-anagide ugbu a | kA | 40,50,63,80,100,125 | |
ogo nchedo | Ihe mkpuchi IP4X, IP2X (ọnụ ụzọ VCB mepere) | ||
Akụkụ ndepụta (obosara/ omimi/ịdị elu) | mm | 650(800,1000) /1500(1300,1670,2000) /2300 | |
Ibu | kg | 500-1200 |
Ihe owuwu ihe osise nke cubicle 630A ~ 1250A
Ihe owuwu ihe osise nke cubicle 1600A ~ 4000A
B.Main technical parameters table for 17.5kV switchgear
Mba. | Aha | Nkeji | Data | |
1 | Egosiri voltaji | kV | 15/17.5 | |
2 | Enyere ọkwa mkpuchi mkpuchi | 1 min ugboro ike na-eguzogide voltaji (RMS) | kV | 50 |
Ọkụ ọkụ na-eguzogide voltaji (elu) | 95 | |||
3 | Enyere ugbu a | A | 630-4000 | |
4 | Enyere mkpirisi okirikiri oghere ugbu a | kA | 50 | |
5 | Ogo ugboro ike | Hz | 50/60 | |
6 | Enyere ọkwa mkpirisi okirikiri na-eme ugbu a(elu) | kA | 130 | |
7 | Ogo kacha elu na-anagide ugbu a | kA | 130 | |
8 | Obere oge na-anagide ugbu a | kA | 50 | |
9 | Ndụ eletrik | ugboro | 20 | |
10 | Edere ogologo oge okirikiri dị ugbu a | s | 4 | |
11 | Ndụ Mechanical nke VCB | ugboro | 10000 | |
12 | Ogo nchekwa nke cubicle | Ihe mkpuchi IP4X, IP2X (ọnụ ụzọ VCB mepere) | ||
13 | Akụkụ ndepụta (W*D*H) | mm | 800/1000*1500/1670*2300 | |
14 | Ibu | kg | 500-1200 |
Nkọwapụta nka nka maka 24kV switchgear
Ihe | Nkeji | Data | |
Egosiri voltaji | kV | 24 | |
Ugboro ugboro | Hz | 50/60 | |
Enyere ugbu a | A | 630,1250, 1600, 2500, 3150, 4000 | |
Enyere ọkwa mkpuchi mkpuchi | 1min ugboro ike (usoro ruo ụwa / gafee kọntaktị mepere emepe) | kV |
65 |
Ọkụ ọkụ na-eguzogide voltaji (usoro ruo ụwa / gafee kọntaktị mepere emepe) | kV |
125 | |
Egotara obere oge nagide ugbu a(4s) | kA | 20, 25, 31.5 | |
Ogo kacha elu na-anagide ugbu a | kA | 50, 63, 80 | |
ogo nchedo | Ihe mkpuchi: IP4X, ụzọ mepere emepe: IP2X | ||
Akụkụ ndepụta (obosara x omimi x ịdị elu) | mm | 1000(800)x1820(1500)x2430(2300) | |
Ibu | kg | 1200-1500 |
1. A ga-atụle ike sekit dị mkpirikpi nke CT iche iche;
2. Eserese nke ahịrị na-apụ apụ n'azụ kwesịrị inwekwu cubicle.